MAC131 Application Controller

Model:MAC131

Multi-Master DALI-2 application controller compliant with IEC 62386-101/-102/-103, with 1 DALI line (built-in bus power supply), standalone & cluster lighting control with zone/scene/schedule management.

  • Multi-Master DALI-2 application controller compliant with IEC 62386-101/-102/-103, receiving events from input devices
  • 1 DALI line(s) with integrated DALI bus power supply, max. 200mA output per line
  • Up to 64 control gears (16 groups) and 64 control devices (instances in up to 32 groups) per DALI line
  • Standalone lighting control: up to 32 zones per unit, 16 fast + 32 slow scenes per zone; scenes combine into schedules (calendar) or timers
  • Cluster lighting control: multiple application controllers work in parallel over Ethernet; zones span controllers and DALI lines
  • Extended DALI-2 protocol supports HVAC / floor-heating gears and temperature/humidity input devices
  • 10M/100M Ethernet (DHCP), one MODBUS-RTU slave and one MODBUS-RTU master interface, DIN-rail mounting

Technical specifications

DALI standardIEC 62386-101:2018 / -102:2018 / -103:2018
DALI lines1
DALI bus power supply250mA built-in per line, disableable via FT button
DALI groups16 physical groups per line; unlimited logical groups across lines
Zones16
Scenes16 per zone
Schedules16 per zone, daily/weekly
Ethernet10/100M Base-T, DHCP
RS4851 port
Power22–26VDC, max. 500mA
Dimensions108(L)×88(W)×65(H)mm, DIN-rail
Operating conditions-20℃ to 45℃, <90% RH non-condensing